Backflow is a reversal of the normal direction of water flow in a water supply plumbing system.

It occurs when the water delivery main is at a lower pressure than the internal plumbing system (back siphonage). Back siphonage can occur when there is a burst or ruptured water main, or due to excessive demand during fire-fighting operations or other periods of high demand.

Backflow can also occur if a water pump, such as a bore pump, is cross connected to the internal water plumbing system, and is pumping bore water at a higher pressure than the water mains pressure (back pressure).

If a property’s drinking water supply is inadvertently connected with a source of pollution, either through a cross connection or simply a hose submerged in a container of liquid, then these pollutants could enter the water supply when there is an overpressure on the private property side or a sudden drop in water mains pressure.

Why install a backflow prevention device?

The community has a right to protection from contaminated water as a result of a backflow incident. Contaminated water can cause health problems or death and because of this, there are obligations under legislation to install a backflow prevention device:

  • Water Services Act 2012
  • Water Services Regulations 2013

Because of the potentially serious nature of a backflow incident we can, in accordance with the regulations, serve an order to you to install backflow devices at your property boundary. These regulations also mean that penalties of up to $5,000 and $500 per day will be issued if you are not compliant.

Under the regulations we also have the power to restrict or disconnect water services to protect the drinking water supply.

Who can install a backflow prevention device?

Only a licensed plumbing contractor may install backflow prevention devices.

When should I install a backflow prevention device?

If you recently applied to us through our BuilderNet portal for a building development application, redevelopment or changes to existing water services then your application may have been assessed for backflow prevention, or your property has been identified as a backflow risk to the scheme water supply.

The following building application types will be assessed for backflow risk:

  • new developments
  • redevelopments of existing facilities
  • changes to any existing water service
  • additions and alterations (includes where no water service applications are included, applicable only if the property has existing meters)
  • multiple residence and/or commercial (includes where no water service applications are included, applicable only if the property has existing meters)
  • any applications that involve a fire service
  • any applications where the minimum water service size applied for is greater than 25mm in size (except fire services, where the backflow advice applies regardless of the service size)

At the time of approval, the applicant will be informed of the property’s initial backflow risk rating. Site-specific activity will determine the final level of backflow risk and for certain commercial and industrial processes may default the property risk rating to high.

New Water Corporation meters 20mm and 25mm in size come with integral dual check valves incorporated within them. This means low risk properties such as residential only; with only metered services (excluding fire services) of this size already have sufficient backflow prevention. Fire services are medium rated regardless of size.

Backflow risk can be classed as low, medium or high as per AS/NZS 3500.1.

  • Low risk – any condition, device or practice in connection with the drinking water supply system that constitutes a nuisance but does not endanger health or cause injury
  • Medium risk – any condition, device or practice in connection with the drinking water supply system that could endanger health
  • High risk – any condition, device or practice in connection with the drinking water supply system that could cause death

How do you determine the backflow risk rating?

At the time of approval of a building development application, redevelopment or changes to existing water services, you'll be informed of the property’s initial backflow risk rating. This determines the type of backflow prevention device to be installed.

Site-specific activity will determine the final backflow risk rating. Certain commercial and industrial processes may default the property risk rating to high. Fire services are medium rated regardless of size. As an owner or occupier, if you are unsure of your property’s initial backflow risk rating, please consult your builder or developer who has been provided with all of the backflow requirements via BuilderNet.

Can I appeal a backflow risk rating?

Yes. If you consider the risk rating assigned to your property is higher than the risk of site-specific activities being carried out, then you may appeal this rating via our backflow prevention risk rating appeal form.

You must consult a suitably qualified licensed plumbing contractor or hydraulic consultant first and submit an appeal form to Water Corporation within 28 days of being advised of the risk rating. We will advise the property owner of the outcome of the review.

The backflow prevention device must be installed on your side of the water connection at the boundary of your property. Devices shouldn't be buried in the ground. Medium and high rated devices shouldn't be installed in a pit or chamber. The installation and ongoing testing and maintenance is the responsibility of the property owner or occupier.

My builder didn't install backflow prevention – what should I do?

It is the property owner or occupier's responsibility to ensure your nominated builder complies with all of the conditional building approvals, which includes the installation of appropriate backflow prevention based on the risk rating of the property.

Registration of the backflow prevention device

All testable backflow prevention devices (those that are medium or high rated) that are installed at the boundary must be registered. This information should be submitted to Water Corporation by a licensed plumbing contractor qualified to install devices no later than 5 working days after the test is carried out.

Backflow prevention device testing and maintenance

Testable backflow prevention devices at the property boundary (those installed on high or medium risk properties and fire services), legally require testing at commissioning, after any maintenance and every 12 months by an accredited tester qualified to test the devices. We will send a reminder to the property owner for these boundary devices.

While testing may be undertaken by an accredited tester, maintenance of the backflow devices is only to be performed by a licensed plumbing contractor. Failure to maintain a backflow device will result in the serving of a non-compliance notice to the property owner or occupier.

Backflow test reports must be submitted online no later than 5 working days after the test is carried out.

We do not manage zone or individual type backflow prevention and does not accept test reports for these types of devices.

Some forms of backflow prevention will reduce water pressure and flow rate downstream of the device. If water pressure and flow rate is critical for the activities on your property, you need to consult with a licensed plumbing contractor or hydraulic consultant before choosing and installing a backflow prevention device.

Irrespective of the risk rating of a property all fire services are rated medium risk and require (as a minimum) medium rated backflow to be installed.

Fire services that were installed prior to 13 May 2010 are not required to install boundary backflow prevention unless the fire service is being altered at the property boundary.